Description

• Plastic (PPE) fire-resistant enclosure (DIN EN 13501). Brackets for wall-mounted installation supplied as standard.
• Front panel made of plastic resin, integrating covers for filters direct access.
• Round duct connection ports, nominal diameter 150 mm.
• 2 EC (brushless) motors, external rotor, with shaft turning in ball bearings to grant a “maintenance free” functioning, each coupled to a backward curved centrifugal impeller; 2 speeds, independently adjustable at the installation.
• High efficiency counter-flow heat exchanger in PS resin.
• Automatic frost-protection to prevent icing on the heat exchanger.
• Automatic, 100% filtered, mechanic by-pass, granting people comfort in the rooms in mid-season or when the outside temperature does not require the action of the heat exchanger.
• Wired control panel with LCD display, which allows:
• to switch on / off the unit;
• the first set-up;
• to set the speed;
• to set the weekly timer;
• to show time and room temperature;
• to monitor the correct product operation (any faults are shown on the display);
• to show the filters status.
• 2 M5 filters (F7 filter for air supply duct available as optional), easy access for periodic maintenance.
• Condense water tray with discharge pipes.
• Possibility of connection to environmental external sensors (available as optional), for automatic functioning control.
Read full descriptionClose description

Technical Data Sheet

  • Absorbed Current max (A)
    1,4
  • Absorbed Power max (W)
    165
  • Filter class
    F5
  • Frequency (Hz)
    50
  • Insulation Class
  • IP
    X2
  • Max ambient temperature for continuous operation (°C)
    25
  • Max Temperature of Exhaust Air (Continuous Operation)
    40
  • Min ambient temperature for continuous operation (°C)
    0
  • Voltage (V)
    230
  • Weight (Kg)
    22
  • Delivery max (l/s)
    100
  • Delivery max (m³/h)
    350
  • Maximum thermal efficiency (%)
    90,5
  • Pressure max (mmH2O)
    90
  • Pressure max (Pa)
    880
  • Sound power level - radiated Lw [dB(A)]
    57,3
  • Sound power level exhaust inlet Lw [dB(A)]
    43,6
  • Sound power level supply outlet Lw [dB(A)]
    60,2
  • Sound pressure level air extraction Lp [dB (A)] 3m - max speed
    23,1
  • Sound pressure level air supply Lp [dB (A)] 3m - max speed
    39,7
  • Sound pressure level radiated Lp [dB (A)] 3m - max speed
    36,8
  • Diametro Ø (mm)
    150
  • Size A (mm)
    712
  • Size B (mm)
    845
  • Size C (mm)
    455
  • Size D (mm)
    700
  • Size E (mm)
    215
  • Size F (mm)
    410
  • Size G (mm)
    220
Interested?
If you are interested in this product, contact us or locate your nearest Vortice dealer.
Documentation
You can see all the documentation relating to this product: price list, information booklet and wiring diagram.

Accessories

Discover accessories related to the product

C TEMP
C TEMP
Environmental sensor for temperature control.
C SMOKE
C SMOKE
Environmental sensor for air quality.
C HCS
C HCS
Environmental sensor for relative humidity control.
C PIR
C PIR
• Passive infrared sensor.
ELECTRIC HEATER 750
ELECTRIC HEATER 750
FTR G3 198X398X15
FTR G3 198X398X15
FTR M5 198X398X15
FTR M5 198X398X15
FTR F7 198X398X15
FTR F7 198X398X15
Cookies help us to provide our services. By using these services, you accept our use of cookies. Info