Description

• Nominal diameter: 600 cm.
• Thermally protected EC (brushless) motor with three-phase power supply (200-480 V / 50-60 Hz).
• Aerodynamically profiled anodized aluminum blades, equipped with winglets that reduce drag caused by tip vortices.
• Control electronics for power management and operation, complete with EMI/EMC filters to prevent the risk of electromagnetic interference, housed in the aluminum casting of the motor covers. The electronics include:
• an isolated RS485 Modbus communication bus, which allows the fan to be integrated into a BMS,
• an isolated analog input for speed regulation via an external potentiometer (optional) or other device operating with a 0-10 V signal.
• Integrated safety system in the electronics, including protection against overcurrent, short circuit, overtemperature, overvoltage, and undervoltage. In compliance with NFPA 72 (National Fire Protection Agency) requirements, the fan control system forces the unit to shut down and immediately lock out upon receiving a water flow signal from the fire alarm system, thus avoiding compromising the effectiveness of any installed sprinklers.
• Steel sheet ceiling installation kit, including a support pole (nominal length 1.5 m), a pair of brackets, and related hardware, supplied as standard. This kit ensures the unit is securely and securely attached to the ceiling in the most common installation methods.
• Optional kit, consisting of 4 tie rods, specifically designed to ensure additional axial stability. The use of this kit is mandatory if the fan's installation location:
• exposes it to gusts of wind,
• exposes it to the risk of accidental collisions with nearby moving machinery or equipment,
• exposes it to the risk of contact with birds,
• is located in a seismic zone or is otherwise subject to significant vibrations (e.g., industrial processes involving hammers, industrial presses).
• Speed can be adjusted via potentiometer or VORT T, VORT T-HCS, VORT T PLUS, and VORT MASTER remote control units (optional).
• Motor protection rating IP65.
Read full descriptionClose description

Technical Data Sheet

  • Frequency (Hz)
    50-60
  • IP
    65
  • Max absorbed power (W)
    850
  • Max ambient temperature for continuous operation (°C)
    50
  • No of blades
    5
  • Nominal current (A)
    2,8 - 1,4
  • Nominal diameter (m)
    6
  • Voltage (V)
    200-480
  • Weight (Kg)
    136
  • Max airflow (m³/h)
    253800
  • Max RPM
    60


* Technical datas above refer to the product powered at 50 Hz.
For values for 60 Hz power supply, please contact the VORTICE Presales Service at prevendita@vortice-italy.com.

  • Size A (mm)
    1600
  • Size B (mm)
    5950
  • Size C (mm)
    2015

Accessories

Discover accessories related to the product

POT-I
POT-I
Potentiometer for industrial HVLS ceiling fans, installation in Standard 503 box.
VORT T
VORT T
Multiple control unit for Vortice HVLS HYPERBLADE ceiling fans. It allows the control of up to 20 fans in manual or automatic mode, depending on the temperature measured by the int...
POT
POT
Potentiometer for installation in Standard DIN box. White colour. Resistance 10 kO. Switch rating: 4 A / 250 Vac - 10 A / 12 Vdc. Protection: IP44 (recessed installation), IP54 (wa...
WP
WP
External anemometer to be connected to the VORT T control unit, useful for the automatic control of the ceiling-fan in case of wind gusts.
USB-C
USB-C
Modbus USB converter compatible with VORT T control unit, useful for remote control of single or multiple ceiling-fans.
VORT T-HCS
VORT T-HCS
Specifically designed for the zootechnical industry, the VORT T-HCS control unit is an optional, wire-connected control device with an LCD display, capable of automatically monitor...
VORT T PLUS
VORT T PLUS
Vort T-PLUS is a device specifically designed for the accurate control of the microclimate of livestock farms. The onboard microcontroller (PLC) has an intuitive user interface wit...
VORT MASTER
VORT MASTER
Specifically designed to be used in the zootechnical industry, the VORT MASTER control unit guarantees the monitoring of the microclimate in cattle breeding facilities (up to 12 ar...
HVLS HYPERBLADE-RD
HVLS HYPERBLADE-RD
Optional kit including four tie-rods, designed to ensure a solid and safe installation. This kit is mandatory in case of strong wind, risk of accidental impact with machines or o...
STF1
STF1
Fixing bracket for steel beams. Option 1.
STF2
STF2
Fixing bracket for steel beams. Option 2
STF3
STF3
Fixing brackets kit for 3m-5m existing structure. Rod not supplied.
STF5
STF5
Fixing bracket kit for omega beam.
STF6
STF6
Fixing bracket kit for joist under windshield (2 m length).
STF4
STF4
Fixing bracket kit supplied with hinge. (3 m length).
C-RH
C-RH
Relative Humidity sensor (RH) that can be combined with the VORT T-HCS and VORT T PLUS control units.
HVLS HYPERBLADE-PL3
HVLS HYPERBLADE-PL3
Pole, length 3 meters, for installation on high ceilings.
STF7
STF7
Fixing bracket kit for laminated beams.
POT DIG
POT DIG
Digital potentiometer for regulating the operating speed of NORDIK HVLS industrial fans. Fans speed percentage adjustment (settable value: from 0% to 100% / OUTPUT: 0-10V). Rever...
TEMP-NTC 10K
TEMP-NTC 10K
Temperature probe that can be combined with VORT T, VORT T-HCS and VORT T PLUS control units.
F-RS485
F-RS485
RC interference filter (DIN rail housing) for VORT T PLUS control unit.
F-RS485 DIN
F-RS485 DIN
DIN rail mounted RC interference filter for VORT T PLUS control unit.
Cookies help us to provide our services. By using these services, you accept our use of cookies. Info