Description
                    •	Fire-resistant expanded polypropylene enclosure with zinc-coated side plates.
•	Duct connection ports of nominal diameter 125 mm.
•	2 x EC brushless motor with shaft turning in ball bearings; 3 speeds, which can be set independently at the moment of installation and monitored from a remote control panel connected by wire, with LCD display.
•	Air flow settable between 85 m3/h and 185 m3/h.
•	Ultra high-efficiency counter-flow type heat exchanger fashioned from moulded plastic (PS).
•	100% by-pass, automatically operated with filtration.
•	Automatically activated system designed to prevent icing of the heat exchanger.
•	Mod-Bus module with RS485 connection port in slave mode
•	Compatible with operation piloted by Vortice ambient sensors: temperature (C TEMP), relative humidity (C HCS), presence (C PIR) and smoke alarm (C SMOKE). With operation interlocked to sensors, the local control functions are inhibited: the appliance continues to operate at minimum speed as long as the reference parameters monitored by the connected field sensors remain below the relative threshold values; when these values are exceeded, the appliance will switch to the maximum speed setting, which is then maintained until such time as normal ambient conditions are restored.
•	2 x F5 filter (alternatively, option of F7 filter on outlet duct).