Description

• Zinc-coated pressed steel enclosure; interior lined with sound-absorbent and fire-resistant material (DIN 13501)
• Nominal diameter for duct connections: 125 mm.
• EC brushless motors with shafts turning in ball bearings, coupled directly to centrifugal impellers; 3 speeds selectable at the moment of installation.
• Air flow settable between 75 m3/h and 200 m3/h.
• Ultra high efficiency cross-flow type heat recovery unit manufactured in plastic (polyethylene).
• 100% by-pass, automatically operated.
• Automatically activated system designed to prevent icing of the heat exchanger.
• 2 x F5 filter (F7 optional)
• Electronic control system
• Tie-bolts for suspended installation supplied as standard
Read full descriptionClose description

Certifications

Energy label Energy label

Technical Data Sheet

  • Absorbed Current max (A)
    1,0
  • Absorbed Power max (W)
    102
  • Frequency (Hz)
    50
  • Max ambient temperature for continuous operation (°C)
    40
  • Nominal Diameter (mm)
    125
  • Voltage (V)
    230
  • Weight (Kg)
    27
  • Delivery max (l/s)
    57,2
  • Delivery max (m³/h)
    206
  • Pressure max (mmH2O)
    43,5
  • Pressure max (Pa)
    426
  • Sound power level - radiated Lw [dB(A)]
    43,1
  • Sound power level exhaust inlet Lw [dB(A)]
    36,5
  • Sound power level supply outlet Lw [dB(A)]
    43,3
  • Sound pressure level air extraction Lp in free field [dB (A)] 3m - max speed
    16,0
  • Sound pressure level air supply Lp in free filed [dB (A)] 3m - max speed
    22,8
  • Sound pressure level radiated Lp in free filed [dB (A)] 3m - max speed
    22,6
  • Supplier's name or trade mark
    Vortice
  • Specific Energy Consumption class SEC in average climate zone
    A
  • Specific Energy Consumption class SEC average [kWh/m2a]
    -36,3
  • Specific Energy Consumption class SEC cold [kWh/m2a]
    -74,7
  • Specific Energy Consumption class SEC warm [kWh/m2a]
    -11,7
  • Declared typology
    UVR-B: bidirezionale
  • Type of drive
    variatore di velocità: VSD
  • Type of heat recovery system HRS
    a recupero
  • Thermal efficiency of heat recovery at reference air flow [%]
    87,8
  • Maximum flow rate [m3/h]
    163
  • Electric power input of the fan drive, including any motor control equipment, at maximum flow rate [W]
    100,0
  • Sound power level LWA [dB(A)]
    43
  • Reference flow rate [m3/s]
    0,0317
  • Reference pressure difference [Pa]
    50
  • SPI [W/(m3/h)]
    0,39474
  • Control factor CTRL
    0,85
  • Control typology
    amb. centralizzato
  • Maximum internal leakage rates [%]
    8,5
  • Maximum external leakage rates [%]
    8,5
  • Mixing rate
    NA
  • Position and description of visual filter warning
    Vedi libretto istruzioni
  • Airflow sensitivity to pressure variations at + 20Pa and – 20 Pa
    NA
  • Indoor/outdoor air tightness [m3/h]
    NA
  • Annual electricity consumption (AEC) [kWh electricity/a]
    402
  • AHS average Annual heating saved [kWh primary energy/a]
    4570
  • AHS cold Annual heating saved [kWh primary energy/a]
    8940
  • AHS warm Annual heating saved [kWh primary energy/a]
    2067
  • Diametro Ø (mm)
    125
  • Size A (mm)
    868
  • Size B (mm)
    643
  • Size C (mm)
    248
  • Size D (mm)
    963,5
  • Size E (mm)
    551
Interested?
If you are interested in this product, contact us or locate your nearest Vortice dealer.
Documentation
You can see all the documentation relating to this product: price list, information booklet and wiring diagram.

Accessories

Discover accessories related to the product

FTR F7 228X224X24
FTR F7 228X224X24
F7 Filter
DCW 250 D.150(BATTERIA FREDDA)
DCW 250 D.150(BATTERIA FREDDA)
C PIR
C PIR
• Passive infrared sensor.
PANNELLO INSTALLATORE SKP10
PANNELLO INSTALLATORE SKP10
Setting of machine parameters during initial installation procedures:
- speeds
- motors independently adjustable
- defrosting
- connection to any externa...