Description

• Sheet steel housing, internally insulated, fire resistant according wit DIN EN 13501.
• High efficiency backward curved centrifugal fans driven by 3 speeds EC (brushless) motors.
• High efficiency plastic cross-counterflow heat exchanger.
• Automatic thermodynamic by-pass.
• Integrated frost protection.
• Nominal diameter of duct connections 125 mm.
• 2xM5 filters (F7 inlet filter available as option), easy to replace.
• Remote, wired control panel allowing:
o To Switch on/off the product
o To select the fan speeds
o To show the filters status
• Brackets for suspended installation.
Read full descriptionClose description

Certifications

Energy label Energy label

Technical Data Sheet

  • Absorbed Current max (A)
    2,0
  • Absorbed Power max (W)
    250
  • Frequency (Hz)
    50
  • Max ambient temperature for continuous operation (°C)
    50
  • Nominal Diameter (mm)
    150
  • Voltage (V)
    230
  • Weight (Kg)
    33
  • Delivery max (l/s)
    105
  • Delivery max (m³/h)
    380
  • Pressure max (mmH2O)
    56,0
  • Pressure max (Pa)
    550
  • Sound power level - radiated Lw [dB(A)]
    51,0
  • Sound power level exhaust inlet Lw [dB(A)]
    37,8
  • Sound power level supply outlet Lw [dB(A)]
    37,2
  • Sound pressure level air extraction Lp in free field [dB (A)] 3m - max speed
    17,3
  • Sound pressure level air supply Lp in free filed [dB (A)] 3m - max speed
    16,7
  • Sound pressure level radiated Lp in free filed [dB (A)] 3m - max speed
    30,5
  • Supplier's name or trade mark
    Vortice
  • Specific Energy Consumption class SEC in average climate zone
    A
  • Declared typology
    UVR-B: bidirezionale
  • Type of drive
    velocità multiple: VM
  • Type of heat recovery system HRS
    a recupero
  • Control factor CTRL
    0,85
  • Control typology
    amb. centralizzato
  • Specific Energy Consumption class SEC average [kWh/m2a]
    -38,0
  • Specific Energy Consumption class SEC cold [kWh/m2a]
    -77,0
  • Specific Energy Consumption class SEC warm [kWh/m2a]
    -13,0
  • Thermal efficiency of heat recovery at reference air flow [%]
    90,4
  • Maximum flow rate [m3/h]
    280
  • Electric power input of the fan drive, including any motor control equipment, at maximum flow rate [W]
    165,0
  • Sound power level LWA [dB(A)]
    51
  • Reference flow rate [m3/s]
    0,0544
  • Reference pressure difference [Pa]
    70
  • SPI [W/(m3/h)]
    0,35204
  • Maximum internal leakage rates [%]
    3,2
  • Maximum external leakage rates [%]
    5,3
  • Mixing rate
    NA
  • Position and description of visual filter warning
    Vedi libretto istruzioni
  • Airflow sensitivity to pressure variations at + 20Pa and – 20 Pa
    NA
  • Indoor/outdoor air tightness [m3/h]
    NA
  • Annual electricity consumption (AEC) [kWh electricity/a]
    364
  • AHS average Annual heating saved [kWh primary energy/a]
    4641
  • AHS cold Annual heating saved [kWh primary energy/a]
    9078
  • AHS warm Annual heating saved [kWh primary energy/a]
    2098
  • Diametro Ø (mm)
    150
  • Size A (mm)
    1183
  • Size B (mm)
    740
  • Size C (mm)
    288
  • Size D (mm)
    1287
  • Size E (mm)
    650
Interested?
If you are interested in this product, contact us or locate your nearest Vortice dealer.
Documentation
You can see all the documentation relating to this product: price list, information booklet and wiring diagram.

Accessories

Discover accessories related to the product

FTR F7 230X250X48
FTR F7 230X250X48
F7 internal filter (single) for HRI-E TWO version.
ELECTRIC HEATER 750
ELECTRIC HEATER 750
Cookies help us to provide our services. By using these services, you accept our use of cookies. Info